Use the links below to transfer the latest EGX200/400 firmware to your Computer. Note: Communication to serial devices through the EGX during firmware updates is not available. Communications should be restored automatically in most Powerlogic Systems.
EGX200 -- The version 6.1 firmware update includes better broadcast/multicast storm resiliency, auto negotiation improvements, serial communications support for Odd parity, and the ability to communicate with ModbusTCP/IP protocol over nonstandard MTU sized Ethernet networks.
To properly update your EGX200:
1. Transfer the version 6.1 firmware file (egx06100.bin) to your Computer.
2. Use FTP to copy the "egx06100.bin" file from your Computer to the EGX (once the file transfer is complete, the EGX will automatically reboot). Refer to the EGX 200/400 Users Guide if you need more information.
3. Allow the EGX to reboot after the file transfer and browse the EGX to confirm v6.1 is displayed.
EGX400 -- Upgrading the EGX400 to version 6.1 provides all the features of the EGX200 mentioned above plus data logging enhancements, increased support for the number of loadable device types (PLT files) from 32 to 64, SMTP client enhancements, and additional device type support for the ION7300.
To properly update your EGX400, the following steps must be followed in order:
1. Browse the EGX to record the device list entries and which devices are being logged.
2. (Optional) Use FTP to retrieve all currently logged data (".log" files) from the EGX. (Note: all logged data will be lost in step 6)
3. Transfer the version 6.1 firmware file (egx06100.bin) to your Computer.
4. Use FTP to copy the "egx06100.bin" file from your Computer to the EGX (once the file transfer is complete, the EGX will automatically reboot). Refer to the EGX 200/400 Users Guide if you need more information.
5. Allow the EGX to reboot after the file transfer and browse the EGX to confirm v6.1 is displayed.
6. Use FTP to delete all ".plt" files from the EGX (this will cause all logged data to also be deleted).
7. Transfer the version 6.1 ZIP file (egx06100.zip) to your Computer.
8. Extract the files from the "egx06100.zip" file to a known location on your Computer.
9. Use FTP to copy all extracted files to the EGX, overwriting all existing files.
10. Browse the EGX and re-setup the device list and logging using what was recorded in step 1.